2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
386 List Manual (LH11), 01/2016, A5E33839529
Notice: The F CPU may only use PROFIsafe telegrams.
Note: Changes only become effective after POWER ON.
Description: Displays the actual station name for the onboard PROFINET interface on the Control Unit.
Description: Displays the actual IP address for the onboard PROFINET interface on the Control Unit.
Description: Displays the actual default gateway for the onboard PROFINET interface on the Control Unit.
Description: Displays the actual subnet mask for the onboard PROFINET interface on the Control Unit.
Description: Displays the actual DHCP mode for the onboard PROFINET interface on the Control Unit.
Value: 0: DHCP off
2: DHCP on, identification using MAC address
3: DHCP on, identification via name of station
Notice: When the DHCP mode is active (parameter value not equal to 0), PROFINET communication via this interface is no
longer possible! However, the interface can be used for commissioning tool such as STARTER or SCOUT.
r8930[0...239] PN Name of Station actual / PN Name Stat act
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r8931[0...3] PN IP address actual / PN IP addr act
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r8932[0...3] PN Default Gateway actual / PN Def Gateway act
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r8933[0...3] PN Subnet Mask actual / PN Subnet Mask act
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r8934 PN DHCP Mode actual / PN DHCP Mode act
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 -