SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
237
2 Parameters
2.2 List of parameters
Description: Sets the proportional gain for the flux controller.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note: The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
Description: Display and connector output for the output of the field weakening controller (synchronous motor).
Index: [0] = PI output
[1] = I output
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the P gain of the field-weakening controller.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Sets an additional setpoint for the field weakening controller.
The value refers to the dynamic voltage reserve (p1574).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note: For a value equal to zero, the field weakening controller is activated when the maximum voltage, calculated with the
average value of the DC link voltage, is reached.
Negative values cause the field weakening controller to intervene earlier, so that the voltage can move away from the
modulation depth limit.
p1590[0...n] Flux controller P gain / Flux controller Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
0.0 999999.0 10.0
r1593[0...1] CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: 6_2 Unit selection: p0505 Func. diagram: 6724
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1594[0...n] Field-weakening controller P gain / Field_ctrl Kp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6724
Min Max Factory setting
0.00 1000.00 0.00
p1595[0...n] Field weakening controller additional setpoint / Field_ctr add_setp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6726
Min Max Factory setting
-80.00 [%] 50.00 [%] 0.00 [%]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals