2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
256 List Manual (LH11), 01/2016, A5E33839529
Dependency: If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without
overcontrol can be selected as modulation type (p1802 = 3). This does not apply to power units PM260.
Refer to: p0230, p0500
Note: When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2, 10), the modulation depth
must be limited using p1803 (default, p1803 < 100 %). The higher the overmodulation, the greater the current ripple
and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Defines the maximum modulation depth.
Dependency: Default setting PM260: 103 %.
Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Sets the filter time constant for the DC link voltage.
This time constant is used to calculate the modulation depth.
p1803[0...n] Maximum modulation depth / Modulat depth max
PM230
PM230_STO
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 120.0 [%] 115.0 [%]
p1803[0...n] Maximum modulation depth / Modulat depth max
PM240 Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1803[0...n] Maximum modulation depth / Modulat depth max
PM250
PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1806[0...n] Filter time constant Vdc correction / T_filt Vdc_corr
PM230
PM230_STO
PM250, PM260
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 0.0 [ms]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals