27
2 Parameters
2.2 List of parameters
Description: Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value: 0: Ready
1: Quick commissioning
2: Power unit commissioning
3: Motor commissioning
5: Technological application/units
15: Data sets
29: Only Siemens int
30: Parameter reset
39: Only Siemens int
49: Only Siemens int
Dependency: Refer to: r3996
Notice: When the parameter is reset to a value of 0, short-term communication interruptions may occur.
Note: The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have
been defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 =
15).
p0010 = 29, 39, 49: Only for internal Siemens use!
Description: Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value: 0: Ready
1: Quick commissioning
2: Power unit commissioning
3: Motor commissioning
5: Technological application/units
15: Data sets
29: Only Siemens int
30: Parameter reset
39: Only Siemens int
49: Only Siemens int
95: Safety Integrated commissioning
Dependency: Refer to: r3996
Notice: When the parameter is reset to a value of 0, short-term communication interruptions may occur.
p0010 Drive commissioning parameter filter / Drv comm. par_filt
CU240B-2
CU240B-2_DP
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2800, 2818
Min Max Factory setting
0 49 1
p0010 Drive commissioning parameter filter / Drv comm. par_filt
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2800, 2818
Min Max Factory setting
0 95 1

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals