2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
422 List Manual (LH11), 01/2016, A5E33839529
Description: CRC via the Node Identifier of a Power Module.
Note: PM: Power Module
Description: Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
Value: 0: [00 hex] Copy function ended
29: [1D hex] Start copy function node identifier
87: [57 hex] Start copy function SI parameters
208: [D0 hex] Start copy function SI basic parameters
Dependency: Refer to: r3996
Notice: When the parameters are copied, short-term communication interruptions may occur.
Note: For value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
For value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9610 --> 9810, p9650 --> p9850, p9651 --> p9851
Description: Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
p9672 SI module identifier Power Module / Module ID PM
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95), T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4294967295 0
p9700 SI copy function / SI copy function
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00D0 hex 0000 hex
p9701 Acknowledge SI data change / Ackn SI data
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00EC hex 0000 hex