SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
49
2 Parameters
2.2 List of parameters
Description: Displays the flux actual value.
Index: [0] = Unsmoothed
[1] = Smoothed
Description: Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
Description: Displays the actual phase voltage.
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
Note: The values are determined from the transistor switch-on duration.
Description: Displays the transformation angle.
Dependency: Refer to: r1778
Note: The transformation angle corresponds to the electrical commutation angle.
Description: Setting the commissioning and control view for various application classes.
Value: 0: Expert
1: Standard Drive Control (SDC)
2: Dynamic Drive Control (DDC)
r0084[0...1] CO: Flux actual value / Flux act val
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6730, 6731
Min Max Factory setting
- [%] - [%] - [%]
r0087 CO: Actual power factor / Cos phi act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r0089[0...2] Actual phase voltage / U_phase act val
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_3 Unit selection: p0505 Func. diagram: 6719
Min Max Factory setting
- [V] - [V] - [V]
r0094 CO: Transformation angle / Transformat_angle
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2005 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [°] - [°] - [°]
p0096 Application class / Appl_class
PM240 Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6019
Min Max Factory setting
0 2 0