2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
318 List Manual (LH11), 01/2016, A5E33839529
Dependency: The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
p2187[0...n] Load monitoring torque threshold 2 upper / M_thresh 2 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2188[0...n] Load monitoring torque threshold 2 lower / M_thresh 2 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2189[0...n] Load monitoring torque threshold 3 upper / M_thresh 3 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2190[0...n] Load monitoring torque threshold 3 lower / M_thresh 3 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals