SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
239
2 Parameters
2.2 List of parameters
Description: Enters the dynamic torque setpoint for the low-speed range for sensorless vector control.
This parameter is entered as a percentage referred to the rated motor torque (r0333).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: When accelerating and braking p1611 is added to p1610 and the resulting total torque is converted into an
appropriate current setpoint and controlled.
For pure accelerating torques, it is always favorable to use the torque pre-control of the speed controller (p1496).
Description: Displays the actual maximum possible electromotive force (EMF) of the separately-excited synchronous motor.
Dependency: The value is the basis for the flux setpoint.
The maximum possible EMF depends on the following factors:
- Actual DC link voltage (r0070).
- Maximum modulation depth (p1803).
- Field-generating and torque-generating current setpoint.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Sets the smoothing time for the current setpoint.
The current setpoint is generated from p1610 and p1611.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: This parameter is only effective in the range where current is injected for sensorless vector control.
Description: Displays the steady-state field generating current setpoint (Id_set).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: For index 1:
Reserved.
p1611[0...n] Additional acceleration torque (sensorless) / M_suppl_accel
Access level: 2 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6700, 6721, 6722,
6726
Min Max Factory setting
0.0 [%] 200.0 [%] 30.0 [%]
r1614 EMF maximum / EMF max
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_1 Unit selection: p0505 Func. diagram: 6725
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1616[0...n] Current setpoint smoothing time / I_set T_smooth
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6721, 6722
Min Max Factory setting
4 [ms] 10000 [ms] 40 [ms]
r1623[0...1] Field-generating current setpoint (steady-state) / Id_set stationary
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: 6_2 Unit selection: p0505 Func. diagram: 6723
Min Max Factory setting
- [Arms] - [Arms] - [Arms]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals