SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
281
2 Parameters
2.2 List of parameters
Value: 0: SINAMICS
1: VIK-NAMUR
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: Every change only becomes effective after a POWER ON.
Description: Displays the PROFIdrive PZD state.
Dependency: Refer to: p2044
Note: When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
Description: Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency: Refer to: r2043
Refer to: F01910
Description: Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Dependency: Refer to: F01910
Note: For controller STOP, the additional monitoring time is not effective.
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
r2043.0...2 BO: PROFIdrive PZD state / PD PZD state
CU240B-2_DP
CU240E-2_DP
CU240E-2 PN
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setpoint failure Yes No -
02 Fieldbus oper Yes No -
p2044 PROFIdrive fault delay / PD fault delay
CU240B-2_DP
CU240E-2_DP
CU240E-2 PN
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
0 [s] 100 [s] 0 [s]
p2047 PROFIBUS additional monitoring time / PB suppl t_monit
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
0 [ms] 20000 [ms] 0 [ms]
r2050[0...11] CO: PROFIBUS PZD receive word / PZD recv word
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: 4000H Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2440, 2468, 9360
Min Max Factory setting
- - -

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals