2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
388 List Manual (LH11), 01/2016, A5E33839529
Description: Displays the IP address of the second PROFINET controller connected with the device via PN onboard.
Description: Sets the profile for Ethernet/IP.
Value: 0: SINAMICS
1: ODVA AC/DC
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
ODVA: Open DeviceNet Vendor Association
Description: Sets the STOP mode for the Ethernet/IP ODVA profile (p8980 = 1).
Value: 0: OFF1
1: OFF2
Dependency: Refer to: p8980
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the scaling for the speed for Ethernet/IP ODVA profile (p8980 = 1).
Value: 123: 32
124: 16
125: 8
126: 4
127: 2
128: 1
129: 0.5
130: 0.25
131: 0.125
132: 0.0625
133: 0.03125
Dependency: Refer to: p8980
r8962[0...3] PN IP Address Remote Controller 2 / IP Addr Rem Ctrl2
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
p8980 Ethernet/IP profile / Eth/IP profile
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2473
Min Max Factory setting
0 1 0
p8981 Ethernet/IP ODVA STOP mode / Eth/IP ODVA STOP
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2473
Min Max Factory setting
0 1 0
p8982 Ethernet/IP ODVA speed scaling / Eth/IP ODVA n scal
CU240E-2 PN
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
123 133 128

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals