2 Parameters
2.2 List of parameters
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
In addition to all of the combinations listed above, using bit 7, the "STO via Power Module terminals" function can be
enabled (this is permissible for r9771.19 = 1).
Dependency: Refer to: p9601, r9871
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
STO: Safe Torque Off
Description: Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 2.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
In addition to all of the combinations listed above, using bit 7, the "STO via Power Module terminals" function can be
enabled (this is permissible for r9771.19 = 1).
Dependency: Refer to: p9601, r9871
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
STO: Safe Torque Off
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable STO via terminals (processor 2) Enable Inhibit 2810
07 Enable Power Module STO Enable Inhibit -
p9801 SI enable functions integrated in the drive (processor 2) / SI enable fct P2
PM240
PM250
PM260
CU240E-2_DP
CU240E-2 PN
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable STO via terminals (processor 2) Enable Inhibit 2810
03 Enable PROFIsafe (processor 2) Enable Inhibit -
07 Enable Power Module STO Enable Inhibit -

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals