2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
162 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the maximum speed for the positive direction.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Display and connector output for the active positive speed limit.
Dependency: Refer to: p1082, p1083, p1085
Description: Sets the signal source for the speed limit of the positive direction.
Description: Sets the speed limit for the negative direction.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Display and connector output for the active negative speed limit.
Dependency: Refer to: p1082, p1086, p1088
Description: Sets the signal source for the speed/velocity limit of the negative direction.
p1083[0...n] CO: Speed limit in positive direction of rotation / n_limit pos
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3050
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 210000.000 [rpm]
r1084 CO: Speed limit positive effective / n_limit pos eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3050, 7958
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1085[0...n] CI: Speed limit in positive direction of rotation / n_limit pos
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3050
Min Max Factory setting
- - 1083[0]
p1086[0...n] CO: Speed limit in negative direction of rotation / n_limit neg
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3050
Min Max Factory setting
-210000.000 [rpm] 0.000 [rpm] -210000.000 [rpm]
r1087 CO: Speed limit negative effective / n_limit neg eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3050, 7958
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1088[0...n] CI: Speed limit in negative direction of rotation / n_limit neg
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3050
Min Max Factory setting
- - 1086[0]