2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
270 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the maximum flux setpoint to measure the saturation characteristic.
Description: Sets the pole position identification technique.
p1980 = 1, 8: The current magnitude is set using p0329.
p1980 = 4, 6: The current magnitude of the first measurement section is set using p0325, the second using p0329.
p1980 = 10: The rated motor current is impressed to align.
The current magnitudes are limited to the rated power unit values.
Value: 1: Voltage pulsing 1st harmonic
4: Voltage pulsing 2-stage
6: Voltage pulsing 2-stage inverse
8: Voltage pulsing 2nd harmonic, inverse
10: DC current injection
Dependency: When commissioning a catalog motor, the technique is automatically selected depending on the motor type being
used.
Refer to: p0325, p0329, p1780
Refer to: F07969
Note: Voltage pulse technique (p1980 = 1, 4) cannot be applied to operation with sine-wave output filters (p0230).
Description: Displays the angular difference between the actual electrical commutation angle and the angle determined by the
pole position identification.
Dependency: Refer to: p0325, p0329, p1980, r1985, r1987
Note: When the pole position identification routine is executed several times, the spread of the measured values can be
determined using this value. At the same position, the spread should be less than 2 degrees electrical.
Description: Displays the saturation characteristic of the pole position identification routine (saturation technique).
Displays the current characteristic of the pole position identification routine (elasticity technique).
Dependency: Refer to: p0325, p0329, p1980, r1984, r1987
p1974 Speed_ctrl_opt saturation characteristic rotor flux maximum / n_opt rot_fl max
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
104 [%] 120 [%] 120 [%]
p1980[0...n] PolID technique / PolID technique
Access level: 3 Calculated: p0340 = 1,3 Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 10 4
r1984 PolID angular difference / PolID ang diff
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [°] - [°] - [°]
r1985 PolID saturation curve / PolID sat_char
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Arms] - [Arms] - [Arms]