Fig. 3-57 2548 – Status word, faults/alarms 1 and 2 (r2139 and r2135)
- 2548 -
Function diagram
87654321
fp_2548_97_61.vsd
Internal control/status words
G120 CU240B/E-2
09.12.2015 V4.7.6
Status word, faults/alarms 1 and 2 (r2139 and r2135)
0
...
11
0
r2139.3
r2139.7
r2135.14
r2135.15
r2135.13
r2135.12
1
r2139.0
r2139.6
r2139.8
...
6
7
8
12
13
14
15
...
3
From the fault buffer [8060.6]
From the alarm buffer [8065.4]
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, power module [8021.8]
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, power module [8021.8]
Status word, faults/alarms 1Bit No.
1 = Acknowledgment running
1 = Fault present
1 = Internal signal 1 present
1 = Alarm present
1 = Internal signal 2 present
1 = Acknowledgment required
Reserved
Reserved
Status word, faults/alarms 2Bit No.
1 = Fault motor overtemperature
1 = Fault, thermal overload, power module
1 = Alarm motor overtemperature
1 = Alarm, thermal overload, power module
ZSW fault/alarm 1
r2139
r2139
ZSW fault/alarm 2
r2135
r2135
Reserved
r2139.1111
1 = Alarm class bit 0
r2139.1212
1 = Maintenance required
13
...
Reserved
r2139.1
1 = Alarm class bit 1
14
15
r2139.13
r2139.14
r2139.15
1 = Maintenance urgently required
1 = Fault gone/can be acknowledged
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the fault buffer [8060.6]
[2510.2]
[2510.2]
[2510.2]
[2510.2]