SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
491
2 Parameters
2.2 List of parameters
Index: [0] = Input pulse I
[1] = Reset input R
Description: Setting parameter for pulse duration T in milliseconds of instance PST 0 of the pulse extension element.
Description: Display parameter for output pulse Q of instance PST 0 of the pulse extension element.
Description: Setting parameter for the run-time group in which the instance PST 0 of the pulse extension element is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance PST 0 within the run-time group set in p20181.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source for input pulse I and the reset input R of instance PST 1 of the pulse extension element.
Index: [0] = Input pulse I
[1] = Reset input R
p20179 PST 0 pulse duration in ms / PST 0 pulse_dur ms
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7234
Min Max Factory setting
0.00 5400000.00 0.00
r20180 BO: PST 0 output Q / PST 0 output Q
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7234
Min Max Factory setting
- - -
p20181 PST 0 run-time group / PST 0 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7234
Min Max Factory setting
5 9999 9999
p20182 PST 0 run sequence / PST 0 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7234
Min Max Factory setting
0 7999 490
p20183[0...1] BI: PST 1 inputs / PST 1 inputs
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7234
Min Max Factory setting
- - 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals