2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
436 List Manual (LH11), 01/2016, A5E33839529
Dependency: Refer to: r9872
Note: For bit 00:
When STO is selected, the cause is displayed in bits 16 ... 21.
For bit 18:
When the bit is set, STO is selected via PROFIsafe.
For bit 19:
For the drive-integrated motion monitoring functions, due to OFF2, no actual value sensing possible.
Description: Displays the Safety Integrated status on processor 1.
Dependency: Refer to: r9872
Note: For bit 00:
When STO is selected, the cause is displayed in bits 16 ... 21.
For bit 18:
When the bit is set, STO is selected via PROFIsafe.
For bit 19:
For the drive-integrated motion monitoring functions, due to OFF2, no actual value sensing possible.
r9772.0...25 CO/BO: SI status (processor 1) / SI status P1
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2804
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO selected on processor 1 Yes No 2810
01 STO active on processor 1 Yes No 2810
07 STO terminal state on processor 1 (Basic
Functions)
High Low -
09 STOP A cannot be acknowledged active Yes No 2802
10 STOP A active Yes No 2802
15 STOP F active Yes No 2802
16 STO cause: Safety comm. mode Yes No -
17 STO cause selection via terminal (Basic
Functions)
Yes No -
18 STO cause: Selection via motion monitoring
functions
Yes No -
19 STO cause actual value missing Yes No -
20 STO cause selection PROFIsafe (Basic
Functions)
Yes No -
21 STO cause selection on the other
monitoring channel
Yes No -
25 STO cause selection via terminal on the
Power Module
Yes No -