SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
103
2 Parameters
2.2 List of parameters
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
The parameter weights the unsaturated component of the quadrature axis flux function.
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the interdependency of the unsaturated component of the quadrature axis current.
Dependency: Refer to: p0634
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the interdependency of the unsaturated component of the direct axis current.
Dependency: Refer to: p0634
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the gradients of the saturated component over the quadrature axis current.
Dependency: Refer to: p0634, p0635, p0636
Description: Sets the current limit.
Dependency: Refer to: r0209, p0323
Note: The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0305. The current limit p0640 is limited to r0209.
The resulting current limit is displayed in r0067 and if required, r0067 is reduced by the thermal model of the power
unit.
p0634[0...n] Q flux flux constant unsaturated / PSIQ KPSI UNSAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [Vsrms] 100.000 [Vsrms] 0.000 [Vsrms]
p0635[0...n] Q flux quadrature axis current constant unsaturated / PSIQ KIQ UNSAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0636[0...n] Q flux direct axis current constant unsaturated / PSIQ KID UNSAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0637[0...n] Q flux flux gradient saturated / PSIQ Grad SAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [mH] 10000.00 [mH] 0.00 [mH]
p0640[0...n] Current limit / Current limit
Access level: 2 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(1, 3), U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6640
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals