2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
328 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the signal source to continually increase the setpoint for the motorized potentiometer of the technology
controller.
The setpoint change (CO: r2250) depends on the set ramp-up time (p2247) and the duration of the signal that is
present (BI: p2235).
Dependency: Refer to: p2236
Description: Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology controller.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency: Refer to: p2235
Description: Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2238
Description: Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2237
Description: Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency: Refer to: p2230
p2235[0...n] BI: Technology controller motorized potentiometer raise setpoint / Tec_ctrl mop raise
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7954
Min Max Factory setting
- - 0
p2236[0...n] BI: Technology controller motorized potentiometer lower setpoint /
Tec_ctrl mop lower
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7954
Min Max Factory setting
- - 0
p2237[0...n] Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7954
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2238[0...n] Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7954
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2240[0...n] Technology controller motorized potentiometer starting value / Tec_ctrl mop start
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7954
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals