SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
69
2 Parameters
2.2 List of parameters
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: This parameter has no significance for induction motors.
For synchronous motors without reluctance torque, a angle of 90 degrees must be set.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Sets the reluctance torque constant for synchronous motors with reluctance torque (e.g. 1FE ... motors).
This parameter has no significance for induction motors.
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: For synchronous motors without reluctance torque, the value 0 must be set.
Description: Sets the current for the pole position identification routine (p1980 = 1).
For a two-stage technique (p1980 = 4), the current is set here for the 2nd phase.
The current of the 1st phase is set in p0325.
Dependency: If a maximum current (p0323) was not parameterized, then p0329 is limited to the rated motor current.
If p0329 is too small in order to determine the pole position (for p1980 = 1), then p0323 must be first parameterized
and significantly greater than p0329.
Refer to: p0325, p1980, r1984, r1985, r1987
Refer to: F07969
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Description: Displays the rated motor slip.
Dependency: The rated slip is calculated from the rated frequency, rated speed and number of pole pairs.
Refer to: p0310, p0311, r0313
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
p0328[0...n] Motor reluctance torque constant / Mot kT_reluctance
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-1000.00 [mH] 1000.00 [mH] 0.00 [mH]
p0329[0...n] Motor pole position identification current / Mot PolID current
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0000 [Arms] 10000.0000 [Arms] 0.0000 [Arms]
r0330[0...n] Rated motor slip / Mot slip_rated
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Hz] - [Hz] - [Hz]