SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
247
2 Parameters
2.2 List of parameters
Description: Displays the status of the motor model.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: For bit 17:
Displays the enabled status of the rugged model feedback (p1784).
The feedback is used to increase the parameter ruggedness of the motor model and is effective in the operating
range of the two-component closed loop current control.
For bit 18:
Displays the status when enabling the differential current feedback in the current model for operation with encoder.
The function is automatically enabled with p1784 > 0 or p1731 > 0. The feedback is used for a rugged change
between the current model and complete machine model with active rugged model feedback and combination
current.
For bit 19:
Displays the currently active stator circuit feedback in current model operation.
For bit 20:
Displays the currently effective increase of the changeover limits by the value p1749 * p1755.
For bit 21:
For a blocked synchronous motor, the speed ramp-function generator is held in the open-loop speed controlled
operating range if the torque setpoint reaches the torque limit and the speed is less than the threshold value in
p2175.
Description: Sets the speed to change over the motor model to encoderless operation.
r1751 Motor model status / MotMod status
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Controlled operation Active Inactive 6721
01 Set ramp-function generator Active Inactive -
02 Stop RsLh adaptation Yes No -
03 Feedback Active Inactive -
05 Holding angle Yes No -
06 Acceleration criterion Active Inactive -
07 Set angular integrator PMSM Yes No -
08 Stop Kt adaptation PMSM Yes No -
09 PolID active PMSM encoderless Yes No -
10 I injection PMSM Yes No -
11 Speed controller output cannot be set to
zero
Yes No -
12 Rs adapt waits Yes No -
13 Motor operation Yes No -
14 Stator frequency sign Positive Negative -
15 Torque sign Motor mode Regenerative mode -
16 Pulse injection active PMSM Yes No -
17 Operation with rugged model feedback Enabled Inhibited -
18 Operation of the current model with current
feedback
Enabled Inhibited -
19 Current feedback in the current model Active Inactive -
20 Rugged increase of the changeover limits Active Inactive -
21 Motor blocked (RFG stop) PMSM No Yes -
p1755[0...n] Motor model changeover speed encoderless operation / MotMod n_chgSnsorl
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 210000.00 [rpm]