2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
468 List Manual (LH11), 01/2016, A5E33839529
Description: Setting parameter for the run-time group in which the instance OR 3 of the OR function block is to be called.
Value: 1: Run-time group 1
2: Run-time group 2
3: Run-time group 3
4: Run-time group 4
5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance OR 3 within the run-time group set in p20060.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source of input quantities I0, I1, I2, I3 of instance XOR 0 of the XOR function block.
Index: [0] = Input I0
[1] = Input I1
[2] = Input I2
[3] = Input I3
Description: Display parameter for binary quantity Q of instance XOR 0 of the XOR function block.
Description: Setting parameter for the run-time group in which the instance XOR 0 of the XOR function block is to be called.
p20060 OR 3 run-time group / OR 3 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7212
Min Max Factory setting
1 9999 9999
p20061 OR 3 run sequence / OR 3 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7212
Min Max Factory setting
0 32000 90
p20062[0...3] BI: XOR 0 inputs / XOR 0 inputs
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7214
Min Max Factory setting
- - 0
r20063 BO: XOR 0 output Q / XOR 0 output Q
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7214
Min Max Factory setting
- - -
p20064 XOR 0 run-time group / XOR 0 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7214
Min Max Factory setting
1 9999 9999

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals