SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
111
2 Parameters
2.2 List of parameters
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency: The type of analog input AIx (voltage or current input) is set using p0756.
Refer to: p0756
Note: AI: Analog Input
T: Terminal
Description: Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: AI: Analog Input
T: Terminal
Description: Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: AI: Analog Input
T: Terminal
Description: Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
p0756[0...1] = 2, 3 corresponds to a current input (r0752, p0757, p0759 are displayed in mA).
In addition, the associated DIP switch must be set.
For the voltage input, DIP switch AI0/1 must be set to "U".
For the current input, DIP switch AI0/1 or AI2 must be set to "I".
Value: 0: Unipolar voltage input (0 V ... +10 V)
1: Unipolar voltage input monitored (+2 V ... +10 V)
2: Unipolar current input (0 mA ... +20 mA)
3: Unipolar current input monitored (+4 mA to +20 mA)
4: Bipolar voltage input (-10 V ... +10 V)
8: No sensor connected
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
p0753[0...1] CU analog inputs smoothing time constant / CU AI T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r0755[0...1] CO: CU analog inputs actual value in percent / CU AI value in %
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
- [%] - [%] - [%]
p0756[0...1] CU analog inputs type / CU AI type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
0 8 [0] 4
[1] 4