2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
248 List Manual (LH11), 01/2016, A5E33839529
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1749, p1756
Notice: The changeover speed represents the steady-state minimum speed up to which the motor model can be used in
sensorless steady-state operation.
If the stability is not adequate close to the changeover speed, it may make sense to increase the parameter value.
On the other hand, very low changeover speeds can negatively impact the stability.
Note: The changeover speed applies for the changeover between open-loop and closed-loop control mode.
Description: Sets the hysteresis for the changeover speed of the motor model for encoderless operation.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1755
Note: The parameter value refers to p1755.
Extremely small hystereses can have a negative impact on the stability in the changeover speed range, and very
high hystereses in the standstill range.
Description: Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled operation
to open-loop controlled operation.
Dependency: The wait time has no significance if the setpoint speed before the ramp-function generator lies in the open-loop
speed controlled operating range. In this case, the change is made without any delay.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1755, p1756
Note: If p1758 is changed, commissioning must be selected in order to validate the value for the blocking monitoring.
Description: Sets the minimum time for a transition from open-loop controlled to closed-loop controlled operation after the lower
changeover speed p1755 * (1 - p1756 / 100 %) has been exceeded.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1755, p1756
Note: With p1759 = 2000 ms, the delay time becomes ineffective and the model changeover is determined by the output
frequency only (changeover for p1755).
p1756 Motor model changeover speed hysteresis encoderless operation /
MotMod n_chgov hys
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6730, 6731
Min Max Factory setting
0.0 [%] 95.0 [%] 50.0 [%]
p1758[0...n] Motor model changeover delay time closed/open-loop control / MotMod t cl_op
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
100 [ms] 10000 [ms] 500 [ms]
p1759[0...n] Motor model changeover delay time open/closed-loop control / MotMod t op_cl
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 2000 [ms] 0 [ms]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals