2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
96 List Manual (LH11), 01/2016, A5E33839529
Dependency: Refer to: p0604, p0605
Refer to: F07011, A07910
Note: With p0606 = 0 s, the timer is de-activated and only the fault threshold is effective.
KTY/PT1000: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC, bimetallic NC contact: The timer minimum value has no special significance.
Description: Sets the timer between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer is started.
If the sensor fault is still present after the timer has expired, a corresponding fault is output.
Notice: The parameterized time is internally rounded-off to an integer multiple of 48 ms.
Note: If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
Description: Sets the system response when the motor temperature reaches the alarm threshold.
Value: 0: No response only alarm no reduction of I_max
1: Messages, reduction of I_max
2: Messages, no reduction of I_max
12: Messages, no reduction of I_max, temperature storage
Dependency: Refer to: p0601, p0604, p0605, p0614, p0615
Refer to: F07011, A07012, A07910
Note: The I_max reduction is not executed for PTC (p0601 = 1) or bimetallic NC contact (p0601 = 4).
The I_max reduction results in a lower output frequency.
If value = 0:
An alarm is output and I_max is not reduced.
If value = 1:
An alarm is output and a timer is started. A fault is output if the alarm is still active after this timer has expired.
- for KTY/PT1000, the following applies: I_max. is reduced
- for PTC, the following is valid: I_max. is not reduced
If value = 2:
An alarm is output and a timer is started. A fault is output if the alarm is still active after this timer has expired.
If value = 12:
Behavior is always the same as for value 2.
For motor temperature monitoring without temperature sensor, when switching off, the model temperature is saved in
a non-volatile fashion. When switching on, the same value (reduced by p0614) is taken into account in the model
calculation. As a consequence, the UL508C specification is fulfilled.
p0607[0...n] Temperature sensor fault timer / Sensor fault time
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: 8016
Min Max Factory setting
0.000 [s] 600.000 [s] 0.100 [s]
p0610[0...n] Motor overtemperature response / Mot temp response
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(3), T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: 8016, 8017, 8018
Min Max Factory setting
0 12 12

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals