2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
286 List Manual (LH11), 01/2016, A5E33839529
Notice: A maximum of 4 indices of the "trace" function can be used.
Description: Display for the maximum interconnected PZD in the receive/send direction
Index 0: receive (r2050, r2060)
Index 1: send (p2051, p2061)
Description: Sets the start for the SIC/SCC telegram (p60122) in the send words (p2051, p2061).
Dependency: Refer to: p0922, p2079, p60122
Note: For setting p0922/p2079, the value is preset to the end of the PZD telegram.
For p0922 equal to 999 and p2079 not equal to 999, the preset value can be increased.
The value must be set again after changing p0922/p2079.
Description: Sets the response for the receive value (r2090) after PZD failure.
Description: Displays the PROFIBUS address of the sender from which the process data (PZD) is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
22 Bit 22 ON OFF -
23 Bit 23 ON OFF -
24 Bit 24 ON OFF -
25 Bit 25 ON OFF -
26 Bit 26 ON OFF -
27 Bit 27 ON OFF -
28 Bit 28 ON OFF -
29 Bit 29 ON OFF -
30 Bit 30 ON OFF -
31 Bit 31 ON OFF -
r2067[0...1] PZD maximum interconnected / PZDmaxIntercon
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p2071 PROFIdrive SIC/SCC start send / SIC/SCC start send
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2423
Min Max Factory setting
0 30 2
p2072 Response receive value after PZD failure / Resp aft PZD fail
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Unconditionally open holding brake (p0855) Freeze value Zero the value -
r2074[0...11] PROFIdrive diagnostics bus address PZD receive / Diag addr recv
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -