2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
50 List Manual (LH11), 01/2016, A5E33839529
Dependency: The parameter is preset when commissioning the system for the first time and for the factory setting, depending on
the power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 12). After the motor data identification, the system
immediately goes into operation.
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note: When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor
data identification as well as the setting of the operating mode and parameterization of the closed-loop control must
be appropriately adapted.
Description: Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value: 0: IEC-Motor (50 Hz, SI units)
1: NEMA motor (60 Hz, US units)
2: NEMA motor (60 Hz, SI units)
Dependency: If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note: The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
Description: Identification of the Control Unit using an LED.
Note: While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
Description: Configuration of the motor when commissioning the motor.
p0100 IEC/NEMA mot stds / IEC/NEMA mot stds
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 2 0
p0124[0...n] CU detection via LED / CU detection LED
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: U, T Scaling: - Dyn. index: PDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p0133[0...n] Motor configuration / Motor config
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor connection type Delta Star -
01 Motor 87 Hz operation Yes No -

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals