SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
415
2 Parameters
2.2 List of parameters
Description: Sets the acceleration limit to filter velocity fluctuations.
If this percentage value is increased, when accelerating, velocity peaks that do not reflect the real velocity
characteristic can occur.
If this value is decreased, and this dampens the velocity peaks when accelerating.
- the value must be increased if C01711 with message value 1043 has occurred.
- the value must be lowered if acceleration procedures have led to an excessive Safety actual velocity.
Recommendation: The setting of this parameter depends on the motor and closed-loop control, and must be newly determined for each
configuration.
To do this, a measurement should be performed while the actual value jumps, and the limit in r9785[0] must be set so
low using p9589, so that it is exceeded by the value in r9785[1] a maximum of four times per second. The actual
value correction filter intervenes at this instant in time. The step is no longer so drastic.
Dependency: Refer to: r9784
Refer to: C01711
Description: Displays the Safety Integrated version for the safe monitoring functions.
Index: [0] = Safety Version (major release)
[1] = Safety Version (minor release)
[2] = Safety Version (baselevel or patch)
[3] = Safety Version (hotfix)
Dependency: Refer to: r9770
Note: Example:
r9590[0] = 2, r9590[1] = 60, r9590[2] = 1, r9590[3] = 0 --> SI Motion version V02.60.01.00
Description: Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 1.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
p9589 SI Motion actual value sensing sensorless accel. limit (P1) / ActVal sl a_lim P1
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
10.00 [%] 3300.00 [%] 100.00 [%]
r9590[0...3] SI Motion version safety motion monitoring (processor 1) / SI Mtn version P1
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p9601 SI enable functions integrated in the drive (processor 1) / SI enable fct P1
PM230_STO
CU240E-2_DP
CU240E-2 PN
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin