2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
180 List Manual (LH11), 01/2016, A5E33839529
Description: Display and connector output for the status for checking and monitoring flying restart states in the vector control
mode.
Note: For bit 00 ... 09:
Used to control internal sequences during the flying restart.
Depending on the motor type (p0300), the number of active bits differs.
For bits 10 ... 15:
Are used to monitor the flying restart sequence.
Description: Sets faults for which automatic restart should not be effective.
Dependency: The setting is only effective for p1210 = 6, 16, 26.
Refer to: p1210
Description: Sets the automatic restart mode (AR).
The parameters must be saved in the non-volatile memory p0971 = 1 in order that the setting becomes effective.
10 Search in the positive direction Yes No -
11 Stop after positive direction Yes No -
12 Stop after negative direction Yes No -
13 No result Yes No -
r1205.0...15 CO/BO: Flying restart vector control status / FlyRest vector st
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Speed adaptation circuit record angle Yes No -
01 Speed adaptation circuit set gain to 0 Yes No -
02 Isd channel enable Yes No -
03 Speed control switched out Yes No -
04 Quadrature arm switched in Yes No -
05 Special transformation active Yes No -
06 Speed adaptation circuit set I comp to 0 Yes No -
07 Current control on Yes No -
08 Isd_set = 0 A Yes No -
09 Frequency held Yes No -
10 Search in the positive direction Yes No -
11 Search Started Yes No -
12 Current impressed Yes No -
13 Search interrupted Yes No -
14 Speed adaptation circuit deviation = 0 Yes No -
15 Speed control activated Yes No -
p1206[0...9] Automatic restart faults not active / AR fault not act
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
p1210 Automatic restart mode / AR mode
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 26 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals