SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
429
2 Parameters
2.2 List of parameters
Description: Displays the necessary setpoint speed limit as a result of the selected motion monitoring functions.
Contrary to the parameterization of the SI limit values, this parameter specifies the motor-side limit value and not the
load-side limit value.
Recommendation: For the ramp-function generator, by appropriately interconnecting the speed limits p1051 and p1052 with r9733[0, 1],
a drive-based setpoint velocity limiting can be realized.
- CI: p1051 = r9733[0]
- CI: p1052 = r9733[1]
Additional limiting can also be activated using connector input p1085 and p1088.
Index: [0] = Setpoint limiting positive
[1] = Setpoint limiting negative
[2] = Setpoint limit absolute
Dependency: For SLS: r9733[0] = p9531[x] x p9533 (converted from the load side to the motor side)
For SDI negative: r9733[0] = 0
For SLS: r9733[1] = - p9531[x] x p9533 (converted from the load side to the motor side)
For SDI positive: r9733[1] = 0
[x] = Selected SLS stage
Conversion factor from the motor side to the load side:
- motor type = rotary and axis type = linear: p9522 / (p9521 x p9520)
- otherwise: p9522 / p9521
Refer to: p9531, p9533
Notice: If p1051 = r9733[0] is interconnected, p1052 = r9733[1] must also be interconnected and vice versa.
If only the absolute value of the setpoint velocity limiting is required, r9733[2] must be interconnected.
Note: If the "SLS" function is not selected, r9733[0] shows p1082 and r9733[1] shows -p1082.
The display in r9733 can be delayed by up to one Safety monitoring clock cycle as compared to the display in r9720
and r9722.
Description: Display and BICO output for status word S_ZSW1B of the safety information channel.
Notice: For bit 07:
An internal event is displayed if a STOP A ... F is active.
The signal state behaves in an opposite way to the PROFIsafe Standard.
Note: This parameter is only supplied with actual values if SI Motion functions are active. For Safety Integrated Basic
Functions (STO), the value is equal to zero.
r9733[0...2] CO: SI Motion setpoint speed limit effective / SI Mtn setp_lim
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 2820, 2824, 3630
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r9734.0...14 CO/BO: SI Safety Info Channel status word S_ZSW1B / SIC S_ZSW1B
PM230_STO
PM240
PM250
PM260
CU240E-2_DP
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO active Yes No -
07 Internal event Yes No -
14 ESR retract requested Yes No -