2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
88 List Manual (LH11), 01/2016, A5E33839529
101 = STANDARD
102 = PERFORMANCE
103 = HIGH PERFORMANCE
104 = ADVANCED LIFETIME
Dependency: Refer to: p0301, p0531, p0532, p1082
Notice: For p0530 = 101, 102, 103, 104, the maximum bearing speed (p0532) is write protected. Write protection is
withdrawn with p0530 = 1.
If p0530 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3). The maximum speed of the bearing is factored into the limit for the maximum speed p1082.
Note: For a motor with DRIVE-CLiQ, p0530 can only be set to 1.
Description: Display and setting the code number of the bearing.
When setting p0301 and p0530 the code number is automatically pre-assigned and is write protected. The
information in p0530 should be observed when removing write protection.
Dependency: Refer to: p0301, p0530, p0532, p1082
Notice: If p0531 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3). The maximum speed of the bearing is factored into the limit for the maximum speed p1082.
Note: p0531 cannot be changed on a motor with DRIVE-CLiQ.
Description: Sets the maximum speed of the bearing.
The following applies when calculating the maximum speed (p1082):
- for p0324 = 0 or p0532 = 0, p0322 is used.
- for p0324 > 0 and p0532 > 0, the minimum value from the two parameters is used.
Dependency: Refer to: p0301, p0322, p0530, p1082
Notice: This parameter is pre-assigned in the case of motors from the motor list (p0301) if a bearing version (p0530) is
selected.
When selecting a catalog motor, this parameter cannot be changed (write protection). The information in p0530
should be observed when removing write protection.
If p0532 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3).
Description: Display and setting the code number of the load gearbox.
p0531[0...n] Bearing code number selection / Bearing codeNo sel
PM240 Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(3) Scaling: - Dyn. index: MDS, p0130
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
p0532[0...n] Bearing maximum speed / Bearing n_max
PM240 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS, p0130
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [rpm] 210000.0 [rpm] 0.0 [rpm]
p0541[0...n] Load gearbox code number / Load grbx CodeNo
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4294967295 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals