EasyManuals Logo

Siemens CU240B-2 List Manual

Siemens CU240B-2
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #479 background imageLoading...
Page #479 background image
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
479
2 Parameters
2.2 List of parameters
Description: Sets the signal source of the factors X0, X1, X2, X3 of instance MUL 1 of the multiplier.
Index: [0] = Factor X0
[1] = Factor X1
[2] = Factor X2
[3] = Factor X3
Description: Display parameter for the product Y = X0 * X1 * X2 * X3 of instance MUL 1 of the multiplier.
Description: Setting parameter for the run-time group in which instance MUL 1 of the multiplier is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance MUL 1 within the run-time group set in p20116.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source of dividend X1 and divisor X2 of instance DIV 0 of the divider.
Index: [0] = Dividend X0
[1] = Divisor X1
p20114[0...3] CI: MUL 1 inputs / MUL 1 inputs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
- - 0
r20115 CO: MUL 1 product Y / MUL 1 product Y
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
- - -
p20116 MUL 1 run-time group / MUL 1 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
5 9999 9999
p20117 MUL 1 run sequence / MUL 1 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
0 32000 280
p20118[0...1] CI: DIV 0 inputs / DIV 0 inputs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
- - 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals