SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
169
2 Parameters
2.2 List of parameters
Note: For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1127 is re-calculated.
If a braking resistor is connected to the DC link (p0219 > 0), then the minimum ramp-down time is automatically
adapted using p1127.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function
generator.
Value: 0: Cont smoothing
1: Discont smoothing
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
PM230
PM230_STO
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
PM230
PM230_STO
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1134[0...n] Ramp-function generator rounding-off type / RFG round-off type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0 1 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals