2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
242 List Manual (LH11), 01/2016, A5E33839529
Description: Displays the limit value for the integral component of the Isd current controller.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Sets the scaling of the quadrature arm decoupling
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note: This parameter is ineffective for sensorless vector control. In this case, p1727 is always used. If p1726 is set to 0,
then the quadrature de-coupling is de-activated. The integral component of the Isd current controller remains
effective in the complete speed control range.
For the closed-loop control of synchronous motors, this parameter is used to scale the current controller de-coupling.
Description: Sets the scaling of quadrature arm decoupling when the voltage limit is reached.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Displays the actual output of the quadrature channel de-coupling for the d axis.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Displays the actual output of the quadrature channel de-coupling for the q axis.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
r1725 Isd controller integral component limit / Isd_ctrl I_limit
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1726[0...n] Quadrature arm decoupling scaling / Transv_decpl scal
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.0 [%] 200.0 [%] 75.0 [%]
p1727[0...n] Quadrature arm decoupling at voltage limit scaling / TrnsvDecplVmaxScal
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.0 [%] 200.0 [%] 50.0 [%]
r1728 De-coupling voltage in-line axis / U_dir-axis_decoupl
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r1729 De-coupling voltage quadrature axis / U_quad_decoupl
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting