4-77
Group 22: PM Motor Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F+P
G
SLV SV
PMS
V
PM
SLV
SLV2
22-19 Reserved
22-20
Offset Angle of the
Magnetic Pole and
PG Origin
0~360
0
deg X X X X O X X *4
22-21
PM Motor Tuning
0: PM Motor Tuning is not
Active.
0 - X X X X O O X
1: Parameter Auto-tune
2: Magnetic Pole
Alignment and Loop
Adjustment
22-22
Fault History of PM
Motor Tuning
0. No Error
0 - X X X X O O X *4
1. Static Magnetic
Alignment Fault
2. Without PG Option
Card
3. Rotation Pole
Alignment is Forced to
Stop
4. Error of Encoder
Feedback Direction
5. Loop Adjustment is
Time out
6. Encoder Error
7. Other Errors of Motor
Tuning
8. Current Abnormity
Occurs when Aligning
Rotation Magnetic
Pole.
9. Current Abnormity
Occurs while Loop
Adjustment.
10.Reserved
11. Stator Resistance
Measurement
Timeout
* PM motor for A510s575/690v is under development.