3-44
Inverter capacity (HP) 40 50 60 75 100 125 150 175 215 250 270
Output rated
Rated output Capacity (KVA)
40.6 50.2 64.5 74.1 103 114 157 176 195 230 258
Heavy Duty
type
H.D.
(150%/1min)
Rated output current (A)
34 42 54 62 86 99 131 147 163 192 216
Maximum applicable motor
*1
HP (KW) for 575v
30
(22)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
150
(110)
200
(150)
200
(150)
Maximum applicable motor
*1
HP (KW) for 690v
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(132)
215
(160)
250
(185)
270
(202)
Rated output Capacity (KVA)
50.2
64.5
74.1
95.6 114 149 176 195 253 258 294
Normal Duty
type
N.D.
(120%/1min)
Rated output current (A)
42 52 62 80 99
125
147
163
212 216 246
Maximum applicable motor
*1
HP (KW) for 575v
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
150
(110)
200
(150)
200
(150)
250
(185)
Maximum applicable motor
*1
HP (KW) for 690v
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(132)
215
(160)
250
(185)
270
(202)
335
(251)
The maximum output voltage (V) 3-phase575/690V
The maximum output frequency (Hz) Based on parameter setting 0.1~599.0 Hz
Power
Rated voltage, frequency
3-phase 575/690v, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
*1: Take TECO standard 4-pole induction motor as the base.
*2: A510S model is designed to use in heavy duty conditions, the factory setting is the HD (Heavy Duty type) mode.
*3: The overload capacity of A510S model HD (Heavy Duty) is 150% / 1min, 200% / 2sec. See the table below for the carrier
frequency default setting and range.
*4: The overload capacity of A510S model ND (Normal Duty) is 120%/1min, carrier range: 2 KHz ~ 16 KHz, the default setting
is 2 KHz. The default setting is 1.5 KHz for 575/690v inverter that over 215hp
*5: If it is greater than default carrier frequency, you need to adjust the load current based on the de-rating curve.
Inverter Voltage and Capacity HD mode
carrier frequency range
HD mode
carrier frequency factory setting
200V class 400V class
1~20HP 1~30HP 2~16KHz 8KHz
25HP - 2~12KHz 6KHz
30~40HP 40~50HP 2~12KHz (*6) 5KHz
50~100HP 60~175HP 2~10KHz (*6) 5KHz
125HP 2~10KHz 4KHz
- 215HP 2~8KHz 3KHz
125~150HP 2~5KHz 5KHz
270-375HP 2~5KHz 4KHz
425HP 2~5KHz 2KHz
Inverter Voltage and Capacity HD mode
carrier frequency range
HD mode
carrier frequency factory setting
575
V
class 690Vclass
1~10HP - 1.5~16KHz 8KHz
15~75HP 15~75HP 1.5~8KHz 4KHz
100~150HP 100~150HP 1.5~6KHz 3KHz
175~270HP 175~270HP 1.5~4KHz 2KHz
*6: If control mode (00-00) is set to 2 (SLV mode) and maximum frequency (01-02) is larger than 80Hz, the carrier frequency
range is 2~8 KHz.