Table 27: M20 Router Chassis Component Alarm Conditions (continued)
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
Yellow Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 55 degrees C, the fans
turned on to full speed, and one
or more fans have failed
Temperature
Yellow Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and the
fans turned on to full speed.
Red Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and a
fan failed. If this condition
persists for more than 4
minutes, the router shuts down.
Red Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 75 degrees C. If this
condition persists for more than
4 minutes, the router shuts
down.
RedFor technical support, open
a support case using the
Case Manager link at
http://www.juniper.net
/support/ or call
1-888-314-JTAC (within
the United States) or
1-408-745-9500 (outside
the United States).
The temperature sensor failed.
Table 28 on page 76 lists the alarms that the chassis components can generate on an
M40 router.
Table 28: M40 Router Chassis Component Alarm Conditions
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
--------------------Change the air filter.Change the air filter.Air filter