Table 33: T640 Router Chassis Component Alarm Conditions (continued)
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
Yellow Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 55 degrees C, the
fans turned on to full speed,
and one or more fans have
failed.
Temperature
Yellow Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and
the fans have been turned on
to full speed.
Red Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and a
fan failed. If this condition
persists for more than 4
minutes, the router shuts
down.
Red Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
Chassis temperature
exceeded 75 degrees C. If this
condition persists for more
than 4 minutes, the router
shuts down.
RedFor technical support,
open a support case
using the Case Manager
link at
http://www.juniper.net
/support/ or call
1-888-314-JTAC (within
the United States) or
1-408-745-9500
(outside the United
States).
The temperature sensor
failed.
Table 34 on page 102 lists the alarms that the chassis components can generate on a
T1600 router.
Table 34: T1600 Router Chassis Component Alarm Conditions
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
------------------------Change the air filter.Change the air filter.Air filter
Copyright © 2012, Juniper Networks, Inc.102
M Series and T Series Routers Monitoring and Troubleshooting Guide