Table 29: M40e or M160 Router Chassis Component Alarm
Conditions (continued)
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
Yellow Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 55 degrees C, the fans
turned on to full speed, and one
or more fans failed.
Temperature
Yellow Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and the
fans turned on to full speed.
Red Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and a fan
failed. If this condition persists
for more than 4 minutes, the
router shuts down.
Red Check the room
temperature.
Check the air filter
and replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 75 degrees C. If this
condition persists for more than
4 minutes, the router shuts down.
RedFor technical
support, open a
support case using
the Case Manager
link at
http://www.juniper.net
/support/ or call
1-888-314-JTAC
(within the United
States) or
1-408-745-9500
(outside the United
States).
The temperature sensor failed.
Table 30 on page 86 lists the alarms that the chassis components can generate on an
M120 router.