SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
17
2 Parameters
2.1 Overview of parameters
Can be changed
The "-" sign indicates that the parameter can be changed in any object state and that the
change will be effective immediately.
The information "C(x), T, U" ((x): optional) means that the parameter can be changed only in
the specified drive unit state and that the change will not take effect until the unit switches to
another state. This can be a single state or multiple states.
The following states are available:
BO: Unsigned8 – – – x
BO: Unsigned16 – – – x
BO: Unsigned32 – – – x
BO: Integer16 – – – x
BO: Integer32 – – – x
BO: FloatingPoint32 – – – –
Table 2-2 Possible combinations of BICO interconnections, continued
BICO input parameter
CI parameter BI parameter
BICO output parameter Unsigned32 /
Integer16
Unsigned32 /
Integer32
Unsigned32 /
FloatingPoint32
Unsigned32 /
Binary
Legend: x :
–:
rxxxx:
BICO interconnection permitted
BICO interconnection not permitted
BICO interconnection is only permitted for the specified CO parameters
• C(x) commissioning C: Commissioning
Drive commissioning is in progress (p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commissioning settings
(p0010 > 0):
• C: Can be changed for all settings p0010 > 0.
• C(x): Can only be changed for the settings p0010 = x.
A modified parameter value does not take effect until drive commissioning mode is
exited with p0010 = 0.
• UOperation U: Run
Pulses are enabled.
• T Ready T: Ready to run
The pulses are not enabled and the status "C(x)" is not active.