Description
Conditions of use for 24 V conductors:
• Ambient temperature: 55°C
• Conductor limit temperature: ≤ 70°C for operation with the rated load current
Carefully observe the following when routing 24 V conductors:
• A maximum of 1 conductor pair may be bundled together.
• 24 V cables must be routed separately from other cables and conductors that can conduct the
operating current.
• 24 V cables must never be routed parallel to power cables.
• 24 V cables as well as power cables should be routed to the components so that they never
cover ventilation slots.
5.7 24V power supply
5.7.1 Using a Control Supply Module
Overview
You can use a Control Supply Module (CSM) for the 24 V infeed in the drive line-up.
Mounting
5.724V power supply
Booksize power units
94 Equipment Manual, 09/2023, A5E53307519B AA