7.8 Technical data
Technical data
Table 7-6 Smart Line Modules D type (16kW and 24kW)
Feature Unit Article number 6SL5130-
6UE21-6AD0 6UE22-4AD0
Power data
Rated power (P
rated
)
at 380V/400V/480V
Maximum power (P
max
)
at 380V/400V/480V
kW
kW
16/16.8/20.2
48/51/61
24/25.3/30
72/76/91
Input data
Line voltage
Line frequency
Electronics power supply
V
Hz
V
3 AC 380 ... 480
50/60
24
Rated current (I
rated
)
Peak current (I
max
)
A
A
29
86
43
129
Output data
DC link voltage
Overvoltage trip
Undervoltage trip
1)
V
V
V
495...720 (typically 1.35xline voltage)
820
360...446
DC link current (I
DC link
)
DC link peak current (I
d max
)
A
A
33
97
49
146
Current-carrying capacity
DC link busbars
24 V DC busbars
A
A
200
20
200
20
Current consumption of the electronics
at 24VDC
A
0.70
0.70
Power loss W 150 200
DC link capacitance
Smart Line Module
Drive line-up, max.
μF
μF
820
20000
940
20000
Power factor cosφ 0.98
Cooling air requirement m
3
/h 77 77
Weight kg 8.2 8.2
Cable lengths m See Chapter "Maximum permissible cable lengths
(Page54)"
1)
Depends on the parameterized line voltage
Smart Line Modules
7.8Technical data
Booksize power units
124 Equipment Manual, 09/2023, A5E53307519B AA