The following overvoltage protection element is recommended:
Overvoltage protection element
Component / cables Manufacturer Article Article number
24V power supply Dehn BVT AVD24 918422
4.10.5.2 Connection example for overvoltage protection elements
Connection example
The position of the connection for the overvoltage protection element is shown in the following
connection example.
To do this, the following conditions must be satised:
• Overvoltage protection elements must always be placed next to the area to be protected,
e.g.at the entry point to the control cabinet.
• All 24 V cables that exit the protected area must be routed through an overvoltage protection
element.
Application planning
4.1024 V DC supply voltage
Booksize power units
52 Equipment Manual, 09/2023, A5E53307519B AA