5. Remove the side covers from the protective 󹪞ap
6. Close the protective 󹪞ap until you hear it snap into place.
11.4.6.6 Mounting the DC link adapter (4 screws)
Overview
For a multi-tier con󹪝guration, if you wish to mount the DC link adapter on the right-hand side of
a 150mm or 200mm wide component, then it is mounted using 4screws.
Requirement
The installation must comply with the following requirements in order to use the DC link adapter:
The component line-up has a two or multi-tier con󹪝guration.
The DC link adapter is supplied with shims. These are required for SINAMICS S120 booksize
components, and are not relevant for mounting on SINAMICS S220 booksize components.
Required tools:
Slotted screwdriver 1.0x5.5mm to release the protective 󹪞ap
Torx screwdriver TX20
Accessories
11.4DC link adapter
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA 303