EasyManua.ls Logo

TECO A510s - Page 136

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-58
Group 12: Monitoring Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
12-11
Output Current of
Current Fault
Display the output current
of current fault
- A O O O O O O O
12-12
Output Voltage of
Current Fault
Display the output voltage
of current fault
- V O O O O O O O
12-13
Output Frequency
of Current Fault
Display the output
frequency of current fault
- Hz O O O O O O O
12-14
DC Voltage of
Current Fault
Display the DC voltage of
current fault
- V O O O O O O O
12-15
Frequency
Command of
Current Fault
Display the frequency
command of current fault
- Hz O O O O O O O
12-16
Frequency
Command
If LED enters this
parameter, it only allows
monitoring frequency
command.
- Hz O O O O O O O
12-17
Output Frequency
Display the current output
frequency
- Hz O O O O O O O
12-18
Output Current
Display the current output
current
- A O O O O O O O
12-19
Output Voltage
Display the current output
voltage
- V O O O O O O O
12-20
DC Voltage (Vdc)
Display the current DC
voltage
- V O O O O O O O
12-21
Output Power (kw)
Display the current output
power
- kW O O O O O O O
12-22
Motor’s Rotation
Speed (rpm)
Display motor’s current
rotation speed
in VF/SLV mode
Motor’s rotation speed =
output power
x(120/motor’s pole
number)
In PG/SV mode, motor’s
rotation speed is
calculated by feedback
frequency.
Max limit is 65535
- rpm O O O O O O O
12-23
Output Power
Factor (Pfo)
Display the current output
power factor
- - O O O O O O O
12-24 Control Mode
Display control mode
0: VF
1: PG
2: SLV
3: SV
4: PSV
5: PMSLV
6: SLV2
- - O O O O O O O
12-25
AI1 Input
Display the current Al1
input
(-10V corresponds to
-100%, 10V corresponds
to 100%,)
- % O O O O O O O

Table of Contents