10-14
LED display Description Possible causes Corrective action
HPErr
Model
selection
error
Inverter capacity setting
error:
Inverter capacity setting
13-00 does not match
the rated voltage.
Inverter capacity setting does
not match voltage class
(13-00).
Check inverter capacity
setting 13-00.
SE07
PG card error
Inverter PG card setting
error.
No PG feedback card installed.
Set wrong type for PM
Encoder Type (22-08)
Install PG feedback card.
Check control mode.
Set right type for PM
Encoder Type (22-08)
and power on again.
SE08
PM Motor
mode error
Inverter rating does not
support the PM Motor
mode.
Inverter rating does not support
PM motor control mode.
Check control mode.
SE09
PI setting
error
Inverter PI setting error
Inverter pulse input selection
(03-30) selection conflicts with
PID source (10-00 and 10-01).
Check pulse input
selection (03-30) and
PID source (10-00 and
10-01).
FB
(flash)
PID
feedback
breaking
PID feedback signal falls
below level specified in
10-12 (PID feedback
loss detection level) for
the time specified in
10-13 (Feedback loss
detection time). Active
when parameter (10-11
= 1).
Feedback signal wire broken
Feedback sensor broken.
Check feedback wiring
Replace feedback
sensor.
USP
(flash)
Unattended
Start
Protection
Unattended Start
Protection (USP) is
enabled (enabled at
power-up.)
USP at power-up (activated
by multi-function digital input)
is enabled. The inverter will
not accept a run command.
While the warning is active the
inverter does not accept a run
command. (See parameter
03-00 - 03-08 = 50).