Table 26: M7i or M10i Router Chassis Component Alarm
Conditions (continued)
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
Yellow Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 55 degrees C, the
fans turned on to full speed,
and one or more fans failed.
Temperature
Yellow Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and
the fans turned on to full
speed.
Red Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 65 degrees C and
a fan failed. If this condition
persists for more than 4
minutes, the router shuts
down.
Red Check the room
temperature.
Check the air filter and
replace it.
Check the air flow.
Check the fan.
The chassis temperature
exceeded 75 degrees C. If this
condition persists for more
than 4 minutes, the router
shuts down.
RedFor technical support, open
a support case using the
Case Manager link at
http://www.juniper.net
/support/ or call
1-888-314-JTAC (within the
United States) or
1-408-745-9500 (outside
the United States).
The temperature sensor
failed.
Table 27 on page 74 lists the alarms that the chassis components can generate on an
M20 router.