Parameters
List of Parameters
1-106
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays active status word of inverter (in binary) and can be used to diagnose which commands are active.
Description: Resetable system run time counter.
r0968 Status word 1 / Status word 1
Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Drive ready Yes No -
01 Drive ready to run Yes No -
02 Drive running Yes No -
03 Drive fault active Yes No -
04 OFF2 active No Yes -
05 OFF3 active No Yes -
06 ON inhibit active Yes No -
07 Drive warning active Yes No -
08 Deviation setpoint / act. value No Yes -
09 PZD control Yes No -
10 f_act >= P1082 (f_max) Yes No -
11 Warning: Motor current/torque limit No Yes -
12 Brake open Yes No -
13 Motor overload No Yes -
14 Motor runs right Yes No -
15 Inverter overload No Yes -
p0969 Resetable system run time counter / Rst counter
Access level: 3 P-Group: Messages Data type: Unsigned32
Quick comm. NO Active: YES Data set: -
Can be changed: T
Min Max Factory setting
0 4294967295 0