Parameters
List of Parameters
1-28
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays actual motor frequency in Hz. This value is available filtered (r0021) and unfiltered (r0063).
Description: Displays actual deviation of speed controller.
This value is calculated from the speed setpoint (r0062) and the actual speed (r0063).
Dependency: Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Description: Displays slip frequency of motor in [%] relative to the rated motor frequency (P0310).
Note: For V/f control, see also P1335 (slip compensation).
Description: Displays actual output frequency in Hz. This value is available filtered (r0024) and unfiltered (r0066).
Note: The output frequency is limited by the values entered in P1080 (min. frequency) and P1082 (max. frequency).
r0063 CO: Act. frequency / Act. frequency
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Hz] Data set: -
V/f
0
1,2
SLVC
(Observer
model)
Encoder
P0400
P1300
160 ms
Act. frequencies:
Act. filtered frequency
Act. frequency
Act. encoder frequency
21,23
20,22
<20
0
P1300 = 21,23 and P0400 = 0 --> F0090
P0408 60
r0313
Act. filtered speed
r0313
60
r0022
r0021
r0063
r0061
,12
r0064 CO: Dev. frequency controller / Dev. freq ctrl
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Hz] Data set: -
r0065 CO: Slip frequency / Slip frequency
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [%] Data set: -
r0066 CO: Act. output frequency / Act. outp freq
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Hz] Data set: -