List of Parameters
Parameters
1-25
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays second status word of inverter (in bit format).
Notice: r0053 Bit01 "f_act > P2167 (f_off)" ==> see parameter P2167
r0053 Bit02 "f_act > P1080 (f_min)" ==> see parameter P1080
r0053 Bit03 "Act. current r0027 >= P2170" ==> see parameter P2170
r0053 Bit04 "f_act > P2155 (f_1)" ==> see parameter P2155
r0053 Bit05 "f_act <= P2155 (f_1)" ==> see parameter P2155
r0053 Bit06 "f_act >= setpoint (f_set)" ==> see parameter P2150
Description: Displays first control word of inverter (in bit format) and can be used to diagnose which commands are active.
Notice: r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
r0053.1...15 CO/BO: Act. status word 2 / Act StatWd2
PM250
PM260
Access level: 2 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
01 f_act > P2167 (f_off) Yes No -
02 f_act > P1080 (f_min) Yes No -
03 Act. current r0027 >= P2170 Yes No -
04 f_act > P2155 (f_1) Yes No -
05 f_act <= P2155 (f_1) Yes No -
06 f_act >= setpoint (f_set) Yes No -
09 Ramping finished Yes No -
10 PID output r2294 == P2292 (PID_min) Yes No -
11 PID output r2294 == P2291 (PID_max) Yes No -
14 Download Dataset 0 from AOP Yes No -
15 Download Dataset 1 from AOP Yes No -
r0054.0...15 CO/BO: Act. control word 1 / Act CtrlWd1
Access level: 3 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OFF2: Electrical stop No Yes -
02 OFF3: Fast stop No Yes -
03 Pulse enable Yes No -
04 RFG enable Yes No -
05 RFG start Yes No -
06 Setpoint enable Yes No -
07 Fault acknowledge Yes No -
08 JOG right Yes No -
09 JOG left Yes No -
10 Control from PLC Yes No -
11 Reverse (setpoint inversion) Yes No -
13 Motor potentiometer MOP up Yes No -
14 Motor potentiometer MOP down Yes No -
15 CDS Bit 0 (Hand/Auto) Yes No -