List of Parameters
Parameters
1-185
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets maximum modulation index.
Note: P1803 = 100 % : Limit for over-control (for ideal inverter without switching delay).
For vector control the modulation limit will be reduced automatically with 4 %.
If a LC-filter is selected (P0230 = 3 or (P0230 = 4 and P234 > 0)), the max. modulation index is set to 100 % if it is
greater than 100 %.
If an internal output filter is installed the modulation depth is limited to 100 % (p0230 = 3 and p1803 <= 100 %).
Description: Configures Vdc filtering and compensation.
Description: Changes direction of motor rotation without changing setpoint polarity.
Values: 0: Forward
1: Reverse the Motor
Dependency: If positive and negative revolution is enabled, frequency setpoint is directly used.
If both positive and negative revolution are disabled, reference value is set to zero.
Note: See P1000 (select frequency setpoint)
Description: Corrects on-state voltage of the IGBTs.
p1803[0...2] Max. modulation / Max. modulation
Access level: 3 P-Group: Converter Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1810 Control word Vdc control / Control word vdc c
Access level: 3 P-Group: Converter Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
- - 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 enable Vdc average filter Yes No -
01 enable Vdc compensation Yes No -
p1820[0...2] Reverse output phase sequence / Rev.outp.phase seq
Access level: 2 P-Group: Modulation Data type: Unsigned16
Quick comm. NO Active: NO Data set: DDS
Can be changed: T
Min Max Factory setting
0 1 0
p1825 On-state voltage of IGBT / On-state voltage
Access level: 4 P-Group: Modulation Data type: Floating Point
Quick comm. NO Active: YES Data set: -
Can be changed: U, T
Min Max Factory setting
0.0 [V] 20.0 [V] 0.9 [V]